Chemical SOP
Microbiology SOP
Warehouse SOP
Manufacturing SOP
Information technology SOP

Fogging in pharma is a whole-room disinfection method where a disinfectant is aerosolized into a fine mist (fog) to cover all exposed surfaces and the air in controlled areas like cleanrooms and sterile production zones. It is an additional step, not a replacement for manual cleaning and routine disinfection.

Below is a practical, pharma-focused detailed write-up you can almost use as a ready article/SOP backbone.


1. What Is Fogging in Pharma?

Fogging (often called fumigation or whole-room bio-decontamination) is the process of dispersing a disinfectant as very fine droplets into a cleanroom or controlled environment so that:

In pharma, fogging is typically used for:


2. Common Types of Fogging Systems

  1. Cold Fogging / ULV (Ultra Low Volume) Fogging
    • Uses mechanical nozzles/rotary discs to generate fine droplets (typically 5–50 µm).
    • Suitable for many pharma cleanrooms and support areas. cleanroomtechnology.com+1
  2. Thermal Fogging
    • Uses heat to vaporize solution into visible fog.
    • Less common in regulated pharma cleanrooms due to material compatibility, heat, and safety concerns.
  3. Vaporized / Ionized Hydrogen Peroxide (VHP / iHP) – often termed fumigation
    • Hydrogen peroxide (often 7–35%) is vaporized or ionized and actively distributed.
    • Offers reproducible, high-level decontamination; commonly validated with Geobacillus stearothermophilus biological indicators (BIs). Pharmaguideline+1

3. Disinfectants Used for Fogging

Typical choices (must be justified in the Contamination Control Strategy – CCS):

Regulatory note: EU GMP Annex 1 (2022) does not mandate fogging but expects a robust, risk-based cleaning & disinfection program, including validated methods and use of sporicidal agents where appropriate. Pharma Now


4. When Is Fogging Used?

Fogging is typically applied:

It is not generally used as a routine, daily disinfection step; regulators (e.g., CDC) caution against routine fogging in healthcare areas due to limited added benefit versus risk, unless justified. CDC


5. Pre-Fogging Requirements (Prerequisites)

Before fogging:

  1. Perform Manual Cleaning First
    • Remove gross soil, dust, and residue with approved detergent/disinfectant.
    • Fogging is not effective on heavy organic load. Pharma Now+1
  2. Verify Area Status
    • Ensure the area is vacant (no personnel).
    • Stop ongoing operations, cover/remove open product and direct contact components.
  3. Protect Sensitive Equipment
    • Cover or remove sensitive electronics, paper records, and corrosion-prone items if not qualified to withstand the agent.
  4. Seal the Area as per Procedure
  5. HVAC Settings
    • Either keep AHU running on a defined cycle (to assist distribution) or switch to a predefined mode (e.g., minimum exhaust) as justified in validation.

6. Typical Fogging Procedure – Step-by-Step

This is a generic outline. Site SOP must be based on actual equipment, agent, and validation data.

  1. Planning & Authorization
    • Initiate fogging via approved request (BMR/BPR reference, deviation CAPA, or planned preventive activity).
    • Verify that the correct disinfectant, batch number, and expiry are available.
  2. Calculate Disinfectant Quantity & Cycle Time
    • Volume of room (m³) × validated dose (e.g., ml/m³ or g/m³) → required quantity.
    • Cycle duration should include dispersion time + minimum contact time (commonly 15–30 min or as per validation for the specific system). cleanroomtechnology.com+1
  3. Place Fogger(s)
  4. Place Indicators (for Validation / Routine Check)
    • Biological indicators (BIs) and/or chemical indicators (CIs) at worst-case locations:
      • Corners, behind equipment, under benches, on high shelves, inside isolator chamber, etc.
    • Common BI: Geobacillus stearothermophilus spore coupons for H₂O₂/VHP systems. Pharmaguideline+1
  5. Start Fogging Cycle
    • Start the fogger and exit the area, ensuring doors are properly closed.
    • Observe status via external indicator or HMI if provided.
  6. Hold / Contact Time
    • Maintain area sealed for validated contact time (e.g., 30–90 min, or as per system).
    • HVAC mode should be the same as used during validation (e.g., reduced exhaust, recirculation, or off). cleanroomtechnology.com+1
  7. Aeration / Ventilation
    • After contact time, start controlled aeration:
      • Open specific vents/doors or use AHU to bring concentration down below occupational exposure limits.
    • Many modern systems monitor H₂O₂ concentration and signal when safe levels are reached. Curis System+1
  8. Post-Fogging Checks & Documentation
    • Retrieve BIs/CIs and send to microbiology for incubation (BIs) or visual reading (CIs).
    • Record:
      • Date, time, area, disinfectant details, quantity, room volume, operator, results of BIs/CIs, deviations, and clearance to use area.

7. Validation and Re-Qualification of Fogging

Fogging must be fully validated as part of the disinfection program:

7.1 Initial Validation

7.2 Ongoing Re-Qualification


8. Advantages of Fogging in Pharma


9. Limitations and Risks

Leave a Reply

Your email address will not be published. Required fields are marked *

error: Content is protected !!